Application (IEC 60502 Low Voltage Cables):
These cables are used for electricity supply in low voltage installation system, They are suitable for installation in indoors and outdoors, in cable ducts, under ground, in power and switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.
Construction(IEC 60502 Low Voltage Cables):
![]() |
| |
|
| |
Conductor: | annealed copper or of plain aluminium or aluminium alloy | |
Insulation: | XLPE / PVC material | |
Armour: | Aluminum/galvanized steel/steel wires applied helically over the Inner Covering as per IEC 60502-1, or double aluminum/steel tapes and copper/tinned copper wire can also be manufactured upon request. | |
Sheath: | PVC compound | |
Sheath colour: | black | |
Insulation Colors (IEC 60502 Low Voltage Cables):
| Colour Code | |
Colour Code (1) | |
1 Core | Red or Black |
2 Cores | Red, Black |
3 Cores | Red, Yellow, Blue |
4 Cores | Red, Yellow, Blue, Black |
5 Cores | Red, Yellow, Blue, Black, Green |
Above 5 Cores | Black Cores with White numerals |
Colour Code (2) | |
1 Core | Brown or Blue |
2 Cores | Brown or Blue |
3 Cores | Brown, Black, Grey |
4 Cores | Blue, Brown, Black, Grey |
5 Cores | Green/Yellow, Blue, Brown, Black, Grey |
Above 5 Cores | Black Cores with White numerals |
Technical data(IEC 60502 Low Voltage Cables):
| Temperature range: | |
during installation: | -5 °C up to +50 °C |
fixed installed: | -30 °C up to +70 °C |
at short circuit of max. 5 s: | up to 160 °C |
Nominal voltage: | Uο/U = 0,6/1 kV |
Test voltage: | 4 kV |
Max. operating voltage in three-phase systems: | 1,2 kV |
Maximal tensile strength: | 50 N/mm² |
Behaviour in fire: | IEC 60332-1 |
Minimal inner bending radius: | |
single core: | 15D |
multi core: | 12D |
Dimensions(IEC 60502 Low Voltage Cables):
Single core(unarmoured)
Nominal | Diameter of Conductor (Approx.) | Nominal | Nominal | Overall Diameter |
mm² | mm | mm | mm | mm |
1x1.5 | 1.4 | 0.7 | 1.4 | 5.6 |
1x2.5 | 1.8 | 0.7 | 1.4 | 6.0 |
1x4 | 2.3 | 0.7 | 1.4 | 6.5 |
1x6 | 2.8 | 0.7 | 1.4 | 7.0 |
1x10 | 3.6 | 0.7 | 1.4 | 7.8 |
1x16 | 4.5 | 0.7 | 1.4 | 8.7 |
1x25 | 5.6 | 0.9 | 1.4 | 10.2 |
1x35 | 6.7 | 0.9 | 1.4 | 11.3 |
1x50 | 8.0 | 1 | 1.4 | 12.8 |
1x70 | 9.4 | 1.1 | 1.4 | 14.4 |
1x95 | 11.0 | 1.1 | 1.5 | 16.1 |
1x120 | 12.4 | 1.2 | 1.5 | 17.8 |
1x150 | 13.8 | 1.4 | 1.6 | 19.8 |
1x185 | 15.3 | 1.6 | 1.6 | 21.8 |
1x240 | 17.5 | 1.7 | 1.7 | 24.4 |
1x300 | 19.5 | 1.8 | 1.8 | 26.7 |
1x400 | 22.6 | 2 | 1.9 | 30.5 |
1x500 | 25.2 | 2.2 | 2.0 | 33.7 |
1x630 | 28.3 | 2.4 | 2.2 | 37.4 |
1x800 | 31.9 | 2.6 | 2.3 | 41.7 |
1x1000 | 35.7 | 2.8 | 2.4 | 46.2 |
Two cores(unarmoured)
Nominal | Diameter of Conductor (Approx.) | Nominal | Nominal | Overall Diameter |
mm² | mm | mm | mm | mm |
2x1.5 | 1.4 | 0.7 | 1.8 | 9.2 |
2x2.5 | 1.8 | 0.7 | 1.8 | 10.0 |
2x4 | 2.3 | 0.7 | 1.8 | 11.0 |
2x6 | 2.8 | 0.7 | 1.8 | 12.0 |
2x10 | 3.6 | 0.7 | 1.8 | 13.6 |
2x16 | 4.5 | 0.7 | 1.8 | 15.4 |
2x25 | 5.6 | 0.9 | 1.8 | 18.4 |
2x35 | 6.7 | 0.9 | 1.8 | 20.6 |
2x50 | 8.0 | 1 | 1.8 | 23.6 |
2x70 | 9.4 | 1.1 | 1.8 | 26.8 |
2x95 | 11.0 | 1.1 | 1.9 | 30.2 |
2x120 | 12.4 | 1.2 | 2.0 | 33.7 |
2x150 | 13.8 | 1.4 | 2.2 | 37.5 |
2x185 | 15.3 | 1.6 | 2.3 | 41.6 |
2x240 | 17.5 | 1.7 | 2.5 | 46.7 |
2x300 | 19.5 | 1.8 | 2.6 | 51.4 |
2x400 | 22.6 | 2 | 2.9 | 58.9 |
Three cores(unarmoured)
Nominal | Diameter of Conductor (Approx.) | Nominal | Nominal | Overall Diameter |
mm² | mm | mm | mm | mm |
3x1.5 | 1.4 | 0.7 | 1.8 | 9.6 |
3x2.5 | 1.8 | 0.7 | 1.8 | 10.5 |
3x4 | 2.3 | 0.7 | 1.8 | 11.6 |
3x6 | 2.8 | 0.7 | 1.8 | 12.6 |
3x10 | 3.6 | 0.7 | 1.8 | 14.4 |
3x16 | 4.5 | 0.7 | 1.8 | 16.3 |
3x25 | 5.6 | 0.9 | 1.8 | 19.5 |
3x35 | 6.7 | 0.9 | 1.8 | 21.9 |
3x50 | 8.0 | 1 | 1.8 | 25.1 |
3x70 | 9.4 | 1.1 | 1.9 | 28.7 |
3x95 | 11.0 | 1.1 | 2.0 | 32.4 |
3x120 | 12.4 | 1.2 | 2.1 | 36.1 |
3x150 | 13.8 | 1.4 | 2.3 | 40.3 |
3x185 | 15.3 | 1.6 | 2.4 | 44.6 |
3x240 | 17.5 | 1.7 | 2.6 | 50.2 |
3x300 | 19.5 | 1.8 | 2.7 | 55.2 |
3x400 | 22.6 | 2 | 3.0 | 63.3 |
Four cores(unarmoured)
Nominal | Diameter of Conductor (Approx.) | Nominal | Nominal | Overall Diameter |
mm² | mm | mm | mm | mm |
4x1.5 | 1.4 | 0.7 | 1.8 | 10.4 |
4x2.5 | 1.8 | 0.7 | 1.8 | 11.3 |
4x4 | 2.3 | 0.7 | 1.8 | 12.5 |
4x6 | 2.8 | 0.7 | 1.8 | 13.7 |
4x10 | 3.6 | 0.7 | 1.8 | 15.7 |
4x16 | 4.5 | 0.7 | 1.8 | 17.8 |
4x25 | 5.6 | 0.9 | 1.8 | 21.5 |
4x35 | 6.7 | 0.9 | 1.8 | 24.1 |
4x50 | 8.0 | 1 | 1.8 | 27.8 |
4x70 | 9.4 | 1.1 | 2.0 | 32.0 |
4x95 | 11.0 | 1.1 | 2.1 | 36.1 |
4x120 | 12.4 | 1.2 | 2.3 | 40.2 |
4x150 | 13.8 | 1.4 | 2.4 | 44.9 |
4x185 | 15.3 | 1.6 | 2.6 | 49.8 |
4x240 | 17.5 | 1.7 | 2.8 | 56.0 |
4x300 | 19.5 | 1.8 | 3.0 | 61.7 |
4x400 | 22.6 | 2 | 3.2 | 70.7 |
Multi-cores(unarmoured)
Nominal | Diameter of Conductor (Approx.) | Nominal | Nominal | Overall Diameter |
mm² | mm | mm | mm | mm |
5x1.5 | 1.4 | 0.7 | 1.8 | 11.2 |
7x1.5 | 1.4 | 0.7 | 1.8 | 12.0 |
10x1.5 | 1.4 | 0.7 | 1.8 | 14.8 |
12x1.5 | 1.4 | 0.7 | 1.8 | 15.2 |
14x1.5 | 1.4 | 0.7 | 1.8 | 16.0 |
19x1.5 | 1.4 | 0.7 | 1.8 | 17.6 |
21x1.5 | 1.4 | 0.7 | 1.8 | 18.4 |
24x1.5 | 1.4 | 0.7 | 1.8 | 20.4 |
30x1.5 | 1.4 | 0.7 | 1.8 | 21.6 |
40x1.5 | 1.4 | 0.7 | 1.8 | 26.0 |
48x1.5 | 1.4 | 0.7 | 1.8 | 26.4 |
61x1.5 | 1.4 | 0.7 | 1.9 | 29.0 |
5x2.5 | 1.8 | 0.7 | 1.8 | 12.2 |
7x2.5 | 1.8 | 0.7 | 1.8 | 13.2 |
10x2.5 | 1.8 | 0.7 | 1.8 | 16.4 |
12x2.5 | 1.8 | 0.7 | 1.8 | 16.9 |
14x2.5 | 1.8 | 0.7 | 1.8 | 17.7 |
19x2.5 | 1.8 | 0.7 | 1.8 | 19.6 |
21x2.5 | 1.8 | 0.7 | 1.8 | 20.6 |
24x2.5 | 1.8 | 0.7 | 1.8 | 22.8 |
30x2.5 | 1.8 | 0.7 | 1.8 | 24.1 |
40x2.5 | 1.8 | 0.7 | 1.9 | 29.4 |
48x2.5 | 1.8 | 0.7 | 1.9 | 29.9 |
61x2.5 | 1.8 | 0.7 | 2.0 | 32.8 |
Package Material (IEC 60502 Low Voltage Cables):
Wooden drum, Steel wooden drum (fumigation)
Cable length in each drum: 500m/1000m or as per actual cable length requirements.
Hot Tags: iec 60502 low voltage cables, China iec 60502 low voltage cables manufacturers, suppliers, factory, electrical extension lead, low voltage heating cable, extension cord wire, power cord ps5, pvc insulated cable, wall extension cord