1.Application:
The three core cables are designed for distribution of electrical power with nominal voltage Uo/U ranging from 3.6/6.6KV to 19/33KV and frequency 50Hz.
They are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations.

2.Technical Data
Conductor: Copper or Aluminum conductor to BS EN 60228:2005 (previously BS6360) Conductor Screen:Semi-conducting material Insulation: XLPE (Cross-Linked Polyethylene) Type GP8 to BS7655 Insulation Screen:Semi-conducting material Metallic Screen:Individual and overall copper tape screen to BS6622 Filler: PETP (Polyethylene Terephthalate) fibres Separator: Binding tape Bedding:PVC (Polyvinyl Chloride) Type TM1 to BS7655 Armored Single core:AWA (Aluminum wire armored) Multi-Core: SWA (Steel Wire Armored) Sheath: PVC (Polyvinyl Chloride) Type TM1 to BS7655 Sheath Colour: Red or Black |
|
3.Product Standard: BS6622 cable

4.Technical parameter
Three Core 6.35/11KV (Um=12KV) | |||||||||||||
Nom. Cross-Section Area | Unarmoured Cables | Steel Wire Armoured Cables | |||||||||||
Nom. Insulation Thickness | Copper Wire Screen Area | Nom. Sheath Thickness | Approx. Overall Diameter | Approx. Weight | Copper Tape Screen Area | Nom. Bedding Thickness | Nom. Armour Wire Diameter | Nom. Sheath Thickness | Approx. Overall Diameter | Approx. Weight | |||
CU | AL | ||||||||||||
CU | AL | ||||||||||||
mm² | mm | mm² | mm | mm | kg/km | mm² | mm | mm | mm | mm | kg/km | ||
25 | 3.4 | 16 | 2.3 | 42.8 | 2600 | 2120 | 3.8 | 1.3 | 2.5 | 2.4 | 50.0 | 4930 | 4400 |
35 | 3.4 | 16 | 2.3 | 45.3 | 3000 | 2320 | 4.1 | 1.3 | 2.5 | 2.5 | 52.3 | 5380 | 4700 |
50 | 3.4 | 16 | 2.4 | 48.5 | 3630 | 2690 | 4.4 | 1.4 | 2.5 | 2.6 | 55.7 | 6210 | 5260 |
70 | 3.4 | 16 | 2.5 | 52.0 | 4440 | 3110 | 4.7 | 1.4 | 2.5 | 2.7 | 59.2 | 7200 | 5870 |
95 | 3.4 | 16 | 2.7 | 56.0 | 5440 | 3620 | 5.2 | 1.5 | 2.5 | 2.8 | 63.2 | 8420 | 6550 |
120 | 3.4 | 16 | 2.8 | 59.4 | 6370 | 4020 | 5.5 | 1.6 | 2.5 | 3.0 | 67.0 | 9580 | 7190 |
150 | 3.4 | 25 | 2.9 | 62.7 | 7430 | 4630 | 5.8 | 1.6 | 2.5 | 3.1 | 70.3 | 10830 | 8030 |
185 | 3.4 | 25 | 3.0 | 66.1 | 8680 | 5150 | 6.2 | 1.7 | 2.5 | 3.2 | 73.9 | 12290 | 8720 |
240 | 3.4 | 25 | 3.1 | 71.7 | 10690 | 5990 | 6.8 | 1.8 | 3.15 | 3.4 | 81.2 | 15620 | 10790 |
300 | 3.4 | 25 | 3.3 | 76.4 | 12770 | 7050 | 7.3 | 1.9 | 3.15 | 3.6 | 86.1 | 18030 | 12240 |
400 | 3.4 | 35 | 3.5 | 85.1 | 16460 | 8680 | 8.0 | 2.0 | 3.15 | 3.8 | 95.0 | 22350 | 14350 |
Three Core 8.7/15KV (Um=17.5KV) | |||||||||||||
Nom. Cross-Section Area | Unarmoured Cables | Steel Wire Armoured Cables | |||||||||||
Nom. Insulation Thickness | Copper Wire Screen Area | Nom. Sheath Thickness | Approx. Overall Diameter | Approx. Weight | Copper Tape Screen Area | Nom. Bedding Thickness | Nom. Armour Wire Diameter | Nom. Sheath Thickness | Approx. Overall Diameter | Approx. Weight | |||
CU | AL | ||||||||||||
CU | AL | ||||||||||||
mm² | mm | mm² | mm | mm | kg/km | mm² | mm | mm | mm | mm | kg/km | ||
25 | 4.5 | 16 | 2.4 | 48.4 | 3000 | 2420 | 4.4 | 1.4 | 2.5 | 2.6 | 55.2 | 5600 | 5100 |
35 | 4.5 | 16 | 2.5 | 50.4 | 3450 | 2670 | 4.7 | 1.4 | 2.5 | 2.7 | 57.6 | 6130 | 5440 |
50 | 4.5 | 16 | 2.6 | 53.7 | 4140 | 3190 | 4.9 | 1.5 | 2.5 | 2.8 | 61.1 | 7010 | 6060 |
70 | 4.5 | 16 | 2.7 | 57.2 | 4980 | 3640 | 5.3 | 1.5 | 2.5 | 2.9 | 64.6 | 8030 | 6700 |
95 | 4.5 | 16 | 2.8 | 60.6 | 5900 | 4050 | 5.7 | 1.6 | 2.5 | 3.0 | 68.2 | 9160 | 7330 |
120 | 4.5 | 16 | 2.9 | 63.9 | 6870 | 4560 | 6.1 | 1.7 | 2.5 | 3.1 | 71.7 | 10340 | 8030 |
150 | 4.5 | 25 | 3.0 | 67.9 | 8030 | 5230 | 6.4 | 1.7 | 2.5 | 3.2 | 75.4 | 11730 | 8930 |
185 | 4.5 | 25 | 3.1 | 71.1 | 9310 | 5770 | 6.8 | 1.8 | 3.15 | 3.4 | 80.6 | 14170 | 10570 |
240 | 4.5 | 25 | 3.3 | 76.9 | 11390 | 6680 | 7.4 | 1.9 | 3.15 | 3.6 | 86.6 | 16670 | 11810 |
300 | 4.5 | 25 | 3.5 | 81.6 | 13510 | 7790 | 7.9 | 2.0 | 3.15 | 3.7 | 91.3 | 19140 | 13340 |
400 | 4.5 | 35 | 3.7 | 89.9 | 17130 | 9340 | 8.5 | 2.1 | 3.15 | 4.0 | 100.0 | 23360 | 15410 |
Three Core 19/33KV (Um=36KV) | |||||||||||||
Nom. Cross-Section Area | Unarmoured Cables | Steel Wire Armoured Cables | |||||||||||
Nom. Insulation Thickness | Copper Wire Screen Area | Nom. Sheath Thickness | Approx. Overall Diameter | Approx. Weight | Copper Tape Screen Area | Nom. Bedding Thickness | Nom. Armour Wire Diameter | Nom. Sheath Thickness | Approx. Overall Diameter | Approx. Weight | |||
CU | AL | ||||||||||||
CU | AL | ||||||||||||
mm² | mm | mm² | mm | mm | kg/km | mm² | mm | mm | mm | mm | kg/km | ||
35 | 8.0 | 16 | 3.1 | 60 | 3750 | 2880 | 6.5 | 1.7 | 2.5 | 3.2 | 74.9 | 9460 | 8700 |
50 | 8.0 | 16 | 3.2 | 65 | 5240 | 4260 | 6.7 | 1.8 | 3.15 | 3.4 | 79.0 | 10620 | 9680 |
70 | 8.0 | 16 | 3.3 | 70 | 6120 | 4730 | 7.1 | 1.8 | 3.15 | 3.5 | 82.5 | 11840 | 10440 |
95 | 8.0 | 16 | 3.4 | 74 | 7140 | 5240 | 7.5 | 1.9 | 3.15 | 3.6 | 86.4 | 13200 | 11350 |
120 | 8.0 | 16 | 3.5 | 77 | 8080 | 5710 | 7.9 | 2.0 | 3.15 | 3.7 | 89.9 | 14520 | 12190 |
150 | 8.0 | 25 | 3.6 | 80 | 9120 | 6220 | 8.2 | 2.0 | 3.15 | 3.8 | 93.6 | 16070 | 13280 |
185 | 8.0 | 25 | 3.7 | 84 | 10440 | 6940 | 8.6 | 2.1 | 3.15 | 3.9 | 97.3 | 17710 | 14090 |
240 | 8.0 | 25 | 3.9 | 91 | 12620 | 8010 | 9.2 | 2.2 | 3.15 | 4.1 | 103.2 | 20370 | 15460 |
300 | 8.0 | 25 | 4.0 | 95 | 14690 | 8800 | 9.7 | 2.3 | 3.15 | 4.3 | 108.2 | 22980 | 17210 |
400 | 8.0 | 35 | 4.3 | 103 | 17720 | 10230 | 10.3 | 2.4 | 3.15 | 4.5 | 116.8 | 27480 | 19450 |
5.Package Material:
Wooden drum, Steel wooden drum (fumigation)
Cable length in each drum: 500m/1000m or as per actual cable length requirements.

Hot Tags: bs6622 cable, China bs6622 cable manufacturers, suppliers, factory, extension cord with usb port, long tv power cable, dc to usb cable, mv 105 5kv cable, ps4 power cord, heavy duty appliance extension cord